Zones and conduits

Module 4 · How a plant network is laid out5 min readBeginner · free

Draw your plant as rooms and doors, and most protection decisions make themselves.

In short

A zone is a group of assets that share the same protection needs, such as all the controllers on one line. A conduit is the path that carries communication between zones, with controls on it. Zones and conduits come from IEC 62443-3-2 and let a plant decide protection per group instead of per device.

Protect groups, not devices

A plant may have thousands of devices. Deciding protection for each one is impossible. Grouping them by function and consequence, such as "line 2 controls", "safety systems", "building management", "historian and reporting", turns thousands of decisions into a dozen.

The path between two zones

Every path between zones: a firewall, a data diode, a serial link, even a person carrying a USB stick. The conduit is where you decide what may cross, in which direction, and how you'll know.

Zones sit across the levels

Purdue levels are horizontal layers. Zones can be drawn within and across them: line 1 and line 2 might both be Level 1, but in separate zones so a problem on one can't spread to the other.

How strong each zone must be

IEC 62443 lets each zone have a target security level (SL 1–4), describing how capable an attacker the zone should withstand. Most zones at private industrial sites sit sensibly at SL 2; safety systems often higher. Lesson 8.1 covers this.

On a real site

A food plant draws five zones: two production lines, utilities, the building system, and the site historian. The first finding is that all five share one flat network. The second is that only four conduits are actually needed. That becomes the segmentation plan.

Easy to mix up

"A zone is a VLAN." A VLAN can implement a zone, but a zone is a design decision about protection needs, not a switch setting.

Check yourself

What is a zone?

A group of assets sharing the same protection needs.

What is a conduit?

A communication path between zones, with controls on it.

Which part of IEC 62443 covers zones and conduits?

IEC 62443-3-2.

Questions people ask

What are zones and conduits in IEC 62443?

Zones group assets with common protection needs; conduits are the controlled paths between them.

How many zones should a plant have?

Enough to separate different functions and consequences, often around five to fifteen for a mid-size site.

Is a firewall a conduit?

A firewall can be part of a conduit; the conduit is the whole communication path and its controls.

Go deeper · from our learning shelf

ICS Virtual Learning Portal CISA · free
Short self-paced courses from the US agency, around an hour each.

Introduction to the World of OT/ICS TryHackMe · free room
How OT works, hands-on, in your browser.

Industrial Cybersecurity On our bookshelf · Pascal Ackerman
Hands-on: architecture with an industrial DMZ, monitoring, threat hunting, assessments and incident response, with lab setups.

See the whole learning shelf: free courses first, then the certificates worth paying for →

Useful? Send it to someone who works near a plant room. Learn OT is free to read, share and teach from.