4–20 mA: the signal that runs most plants
The most trusted signal in industry is a small electric current on a pair of wires.
In short
4–20 mA is the standard way a field instrument sends a measurement to a controller: a small current on two wires, where 4 mA means the bottom of the range and 20 mA the top. Current doesn't fade over long cables, and because zero is 4 mA, a broken wire is obvious. HART adds digital data on top.
A current on two wires
A transmitter, say a pressure transmitter on a pipe, controls how much current flows in a loop of two wires. If its range is 0–10 bar, then 4 mA means 0 bar, 12 mA means 5 bar and 20 mA means 10 bar. The controller's input card measures the current and converts it back into a number.
Current survives distance
Current is the same everywhere in a series loop, so a long cable across a plant doesn't change the reading the way it would change a voltage. It is also less affected by electrical noise from motors and drives.
Four milliamps means alive
So that 0 mA means something is wrong. A broken wire or dead instrument reads 0, which is outside the valid range, and the controller can raise an alarm instead of believing the tank is empty. The 4 mA also powers many instruments down the same two wires.
Digital riding on the analogue
HART layers a small digital signal on top of the 4–20 mA current. The analogue current still carries the main measurement; the digital part lets a technician read the device's tag, range and diagnostics without disconnecting anything.
Still the backbone of most plants
Because it is still everywhere. Even in plants with modern networks, the last few metres from many sensors and valves are often 4–20 mA. It is simple, robust and very hard to tamper with remotely: there is no network address on a pair of wires.
On a real site
A technician checking a suspicious level reading clips a meter onto the loop: 3.6 mA. Below 4 means a fault, not an empty tank. The cable gland has let water in. The controller had already flagged the input as bad, exactly as designed.
Easy to mix up
"4–20 mA is outdated." It is old, not outdated. New plants still use it for many instruments because it is simple and reliable.
Check yourself
On a 0–10 bar transmitter, what pressure does 12 mA mean?
5 bar, halfway along the 4–20 mA range.
Why is a reading of 0 mA useful?
It is outside the valid range, so it signals a broken wire or failed instrument rather than a real zero.
What does HART add?
Digital information (tag, range, diagnostics) carried on top of the analogue current.
Questions people ask
What does 4–20 mA mean?
An analogue signalling standard where a current of 4 mA represents the bottom of a measurement range and 20 mA the top.
Why is 4–20 mA used instead of 0–20 mA?
Starting at 4 mA makes a broken wire (0 mA) detectable and lets the loop power the instrument.
Is 4–20 mA digital?
No, it is analogue. HART adds a digital signal on top of it.
Terms in this lesson
Go deeper · from our learning shelf
ICS Virtual Learning Portal CISA · free
Short self-paced courses from the US agency, around an hour each.
Introduction to the World of OT/ICS TryHackMe · free room
How OT works, hands-on, in your browser.
Industrial Network Security On our bookshelf · Eric D. Knapp
A thorough guide to industrial networks, protocols and how to protect them.
See the whole learning shelf: free courses first, then the certificates worth paying for →
Useful? Send it to someone who works near a plant room. Learn OT is free to read, share and teach from.