Injection moulding hall with a machine control cabinet open beside the press

PLA · Plastics & Packaging

Learn OT · Lesson 6.3

The cabinet walk-down

Module 6 · Knowing what you have5 min readBeginner · free

Some findings never appear on a network. You have to open the cabinet door.

In short

A cabinet walk-down is a physical inspection of control panels, network cabinets and plant rooms, done with the people who maintain them. It finds what passive capture can't: modems with antennas, unmanaged switches, serial links, key switches in the wrong position and passwords on stickers.

Cabinets hide what networks can't

Because networks only show what talks over them, and drawings only show what was drawn. Cabinets show what is actually there.

The checklist

  • Every network device: switches (managed or not), routers, converters, firewalls.
  • Anything with an antenna: cellular modems, Wi-Fi, radio.
  • Labels and stickers: device names, IP addresses, passwords.
  • Controller key switches: run, program or remote?
  • Spare and loose cables plugged into switches.
  • Laptops or PCs left in panels or under desks.
  • Photos of everything, matched to the inventory afterwards.

Bring the person with the keys

A technician who knows the panels, and someone from operations who can say what each one does for the process. Never open live panels without the site's permission and safety rules.

On a real site

A walk-down of one compressor house finds a 4G router taped inside a cabinet door, an unmanaged switch with three unlabelled cables, and the HMI password written on the frame. None of them appeared in the network capture.

Easy to mix up

"The drawings show us what's there." Drawings show what was designed. Walk-downs show what was built and added.

Check yourself

Name three things a walk-down finds that capture doesn't.

Any three of: modems with antennas, unmanaged switches, serial links, key switch positions, password stickers, hidden laptops.

Who should join a walk-down?

A technician who knows the panels and someone from operations.

What should you record?

Photos of everything, matched to the inventory.

Questions people ask

What is a walk-down in OT?

A physical inspection of control cabinets and plant rooms to record what is actually installed.

What should you check in a control cabinet?

Network devices, antennas, labels and stickers, key switch positions and loose cables.

Is a walk-down safe?

Yes, when done with site permission and following the site's electrical safety rules.

Go deeper · from our learning shelf

ICS Virtual Learning Portal CISA · free
Short self-paced courses from the US agency, around an hour each.

Introduction to the World of OT/ICS TryHackMe · free room
How OT works, hands-on, in your browser.

Countering Cyber Sabotage On our bookshelf · Andrew A. Bochman
Idaho National Laboratory's consequence-driven method (CCE): start from the worst things that could happen to your most important functions and work backwards.

See the whole learning shelf: free courses first, then the certificates worth paying for →

Useful? Send it to someone who works near a plant room. Learn OT is free to read, share and teach from.